Products You Can Trust
Whatever your need may be, you can trust that you’re installing a product that is produced to the highest standards.
Learn MoreUse a mild acid solution – CLR mixed with 50% water, White Vinegar mixed with 50% water Fernox DS-40, rinse with cold water completely. Flush using a cleaning solution with a transfer pump or a sump pump inside of the bucket.
E-14 is a disturbance on the low voltage side of the system. This is separated into two parts.
1.) The unit resets and begins to work. E 14 returns in an un-predictable time frame.
2.) Does the unit reset, but goes to E 14 within 5 seconds. This is often caused by the dry contact in the aqua-stat in the domestic water heater. The dry contact water heater’s aqua-stat should be replaced with a PSRKIT-22 Triangle Tube IDHS. This will now allow the boiler to see the actual temperature in the tank and determining when to go into water heating operation.
This disturbance is far more difficult to pinpoint. It is important to be sure that the reset is working. When the reset button is pressed and released, the E-14 should disappear, and a software code show up, once that clears, the E-14 will re-appear we now know the reset works. Remove the entire field wires connected to terminals 7 through 19. Try to reset the boiler. If the E14 goes away, one by one re-install the field to see what field device is affecting the boiler. Remove the X04 plug from the MCBA module. (This is the plug with 2 blue wires and 1 yellow wire. Be sure to look carefully how the plug is connected and when re-connecting it, be sure to put it back the same way you removed it.) Reset the boiler, if the E-14 goes away and is replaced with a b-40 and a 9-## reconnect the X04, if it immediately goes to E14. We now have isolated the fault.
Since the E14 stopped when the X04 was removed and now is back in place. Remove the 2 yellow wires from the flue sensor, reset the boiler. If the b-40 and 9## returns, replace the flue sensor. If the E-14 comes right back, replace the wires on the flue sensor, then remove the wires in the top of terminals 17 and 18 (one has a blue and a yellow wire in it, the other has a single blue) let them hang in the air, reset the boiler. If the fault clears, isolate and insulate each of the wires. They are not being used, so they may remain isolated and insulatedIf the E-14 does not disappear when the X04 is removed remove the X05 plug. Then reset the boiler, if the boiler resets and shows the b40 and the 9##, then replace the X04, reset the boiler and operation should commence. This is an indication that there is a problem with the outdoor sensor or the wire for the outdoor sensor.
This error will occur if the boiler supply water temperature exceeds 212ºF.
The following items should be checked:
The cause can be traced to just a few basic conditions.
1.) Remove and inspect the igniter. Igniters are consumable. After many ignitions and or subjection to high temperatures, it may be recommended to replace the igniter when you have failed ignition issues.
2.) Check the connections of the igniter wire, be sure they are strong connections and that the wire is not in contact with any metal surface.
3.) Remove the air intake pipe from the burner, inspect the venturi, feel the inside rim of the air inlet hole, it should be pristine, tight in the shroud, no holes, no breaks, no cracks. A large amount of black residue inside the venture would indicate the venturi has started too broken down and needs to be replaced.
4.) With the gas valve turned off, check the incoming gas pressure on the gas valve of the unit. N.G should have approximately 6 to 7 inches and L.P should be approximately 11 inches. When the gas valve opens for ignition, the pressure is not allowed to deviate more than one inch W.C.
5.) A final test if we cannot create fire, attach the manometer to the outlet port of the gas valve. During the pre-purge you must develop 1.5 to 2 inches W.C. at a minimum to pull gas through the gas valve. If we are not developing the correct negative pressure, the system may be blocked in the combustion area or exhaust lines, or the blower is not developing the correct amount of airflow.
This will occur when you have two conditions. Depending on a start up or a unit that has been in service, will determine the direction to take.
1.) Remove the igniter and reset the controller. If the fault will not reset, then unplug the gas valve and reset again. If the unit will not reset, replace the control module. Be sure to test the resistance of the gas valve, these are 120 volt gas valves and should have approximately 375 ohm resistance on one coil, and 717 ohms on a second coil.
2.) If the controller resets, replace the igniter and also replace the insulation block. There will be an alignment tool, be sure to use to install the insulation block.
This error will occur if during the ignition sequence the blower does not start.
The boiler display will indicate a status code of 5 during the ignition sequence for 4 minutes before locking out.
Check to see if a sensor is far out of calibration or moving in a direction un-compatible with the process that the controller is presently running. With the unit off for at least 1 hour, go to the Info mode of the boiler. Look at steps 1, 2 and 5. These values should be within 10 degrees of each other. If a vast difference, there is a strong possibility of the sensor out calibration causing the issue.
When the unit is heating, it is important that the supply sensor is higher than the return and the flue, the flue is lower than the supply and higher than the return, and the return should be the lowest. Once the burner is off, the flue should become lower than the return. A true short in either coil of the gas valve will also give the e44, but will not reset under any condition, and is many times fatal to the MCBA. This will require an ohm check of the gas valve coil. The gas valve should have a 32 ohm reading on coil 1 and 18 ohms on the second coil. The rectifier head on the gas valve may also be shorted, requiring all three parts (gas valve, rectifier head, and MCBA) to be replaced.
Start the boiler and set the boiler into HIGH fire. Hold in the “Mode” and the “+” buttons simultaneously until the first digit flashes “H” Remove the cap in the exhaust flue pipe; install the probe of the analyzer into the exhaust flue pipe hole in the flue pipe. If the O2 reading is above 3.9% turn throttle screw CCW to lower the O2, if the reading is below 3.9% turn the throttle CW to increase the O2. Set the boiler into LOW fire. Hold in the “Mode” and the “-” buttons simultaneously until the first digit flashes “L”. Check the O2 reading in low fire, it should not differ more then 2/10 of a percent. If the readings between High and LOW fire differ more then 2/10 %, call Triangle Tube Tech Support.
Use a mild acid solution – CLR mixed with 50% water, White Vinegar mixed with 50% water Fernox DS-40, rinse with cold water completely. Flush using a cleaning solution with a transfer pump or a sump pump inside of the bucket
The Tank-in-Tank is a stainless steel hot water tank (cylinder) entirely immersed within an outer tank which contains the primary water. The corrugated inner stainless steel tank forms a large heat exchange surface that can heat the domestic hot water in a very short time. The outer tank is covered with a high-quality insulation, protected by a shock resistant plastic jacket.
The decision to use stainless steel for the manufacture of the "Tank in Tank" was made in the 60's. It was chosen for its well established reliability and advantages over other materials, namely: Stainless steel is stable at elevated temperatures above 180ºF, which is not the case for tanks manufactured from mild steel protected by a glass lined coating. It is for this reason that some manufacturers include a clause in their guarantee limiting the DHW storage temperatures to 140°F or even 130°F.
Stainless steel, as its name suggests, is resistant to corrosion. The protective coatings in an enameled tank can be damaged by a shock during transportation, unloading or maneuvering it into position. This is not the case with stainless steel.
Last, but not least, a stainless steel tank does not need a sacrificial anode. This is a major advantage versus conventional water heaters. Stainless steel is also universally recognized for its hygienic properties and is frequently used in the manufacture of items for the food industry and for surgical instruments. There is little chance of its use being questioned on the basis of it being a health hazard. Conversely, protective coatings, i.e. enameling cannot be examined everyday and their failure could lead to unhealthy consequences.
When the thermostat in the inner tank calls for heat, the boiler and circulator start. Boiler water is circulated around the outer tank and heats the domestic water in the inner tank. After transferring its heat, boiler water is returned to the boiler to be re-heated. When the thermostat in the inner tank reaches its preset mark, the boiler and circulator shut off.
Water contains dissolved minerals such as calcium-carbonate, magnesium, silica, iron and phosphates. When water is heated, it undergoes a chemical reaction that causes these dissolved minerals to precipitate out as solids. These solid minerals (specifically calcium and magnesium) are called lime-scale. Lime-scale is a poor conductor of heat. If lime-scale collects on the heat transfer surfaces of a water heater's heat exchanger, it insulates the heat from the water. This means less heat is transferred into the water and more money is spent heating the lime-scale instead of the water.
Triangle Tube's Indirect water heater's were specially designed to prevent the formation of lime scale on the surface of the exchanger, thus retaining high performance throughout the product's lifetime.
There are three key benefits to using a Tank-In-Tank System:
1.) High Efficiency Hot Water: Thanks to the exceptionally large heating surface area (typically 1.5 to 2.5 times greater than a coil), Tank-in-Tank systems can use the whole heating power of the boiler. Consequently the Tank-in-Tank can heat a large quantity of domestic hot water in an exceptionally short time. As a result of this rapid heating capacity, the volume of stored water can be reduced and energy loss kept to a minimum. Furthermore, condensing boilers benefit from being able to work in condensing mode for much longer, giving much greater fuel efficiency.
2.) Self-Descaling: The tank is free to expand and contract as a result of the variations in pressure which occur with every hot water draw-off. The corrugations amplify these movements and prevent the formation of lime scale on the surface of the exchanger,which retains its high performance throughout its service life. The Tank-in-Tank requires no anode protection and the self-descaling feature eliminates the need for regular descaling. A primary coil is not required and there is no need to worry about contamination, leaking and sludging caused by cracked linings.
3.) Anti-Legionellae: Natural turbulence across the concave base keeps particles in suspension, preventing formation of sediment and - aided by consistently high store temperatures (above 140 F) - helps to avoid growth of legionellae bacteria. In a tank with a coil, the water at the bottom remains tepid; so the legionellae can survive and multiply.
Use a mild acid solution – CLR mixed with 50% water, White Vinegar mixed with 50% water Fernox DS-40, rinse with cold water completely. Flush using a cleaning solution with a transfer pump or a sump pump inside of the bucket.
Sensor drift comes about when separation between the supply and return sensor is changing too quickly. This occurs when the burner is operating, the supply temp is increasing but the return temp is not increasing at a reasonable rate. Since your boiler is in lockout, push the up button before you reset the boiler and see that your supply and return sensor are equal.
Normal reason for the drift is a lack of flow through the heat exchanger; either the pump is undersized, restricted, or there's a small air pocket in the top of the heat exchanger. Check for power to the pump, be sure the pump is running, and check the piping for a restriction in the system. Look in the alarm history and see what process the boiler was in when the lockout occurred. See if the flow is halted before the post pump operation has occurred.
This error will occur if power to the boiler is lost after a lockout has occurred. The boiler must be manually reset and the original lockout code will be lost. If you push the reset button and an E-4-04 instantly re-appears, the system is in a hard lockout.
To remove from hard lockout; take a metal object and short out the first set on pins on the left hand side, top to bottom for two seconds.
This will occur when the display and the control module stop communicating.
1.) Remove all field control wiring. Attempt a reset, if the fault ends, find the problem in the external controls.
2.) With the removed field wiring removed if the error remains, remove the X06, the X03 and the nX07 from the boiler in question. Reset the control. If the boiler resets, then we need to know which plug is giving us the fault. At this point contact tech support.
3.) With the X06, X07, X03 removed, the fault will not reset, and then replace the control module. If this is part of a cascade system contact Tech Support before you proceed.
1.) From the home screen, push and release the small round button to the left of the left arrow key.
2.) The request for an installer access code will be prompted, this access code is “054." Use the left and right keys to move the cursor and the up and down to change the digit.
3.) Once "054" is entered, you be in the advanced parameters. Use the boiler manual or the Tri-Max control supplement to change the actions.
1.) Be sure that the boiler combustion and temperature indications are correct. See trend sheet for assistance.
2.) Be sure that all of the settings in the controller are correct. Refer to the correct manual for setting instructions.
3.) Be sure that there is a completely filled tank and boiler heat exchanger is free of air.
4.) Remove the actuator head off the diverting valve inside the boiler cabinet. Be sure that the spring has driven the cage completely to the top of the valve. If it is not completely at the top, grab the stem with pliers and apply a small amount of force to get the valve to seat. If the cage moves and seats, rebuild the valve and chemically clean the heating system.
5.) Using a 5 Gal. bucket marked 2/3 of the way to the top. With the tank cold, go to the largest tap in the home (normally the bath tub) and open it full. Then close the cold water feed to the water heater to a point that it takes the fixture 1 min to fill the bucket from empty to the mark. This will insure we are not moving more than 3GPM through the water heater.
6.) All A.S.S.E. mixing valves will fail to the cold side. If the tank is hot and the outlet of the valve cold, the mixing valve is either fouled or stuck, either way you have to replace the valve.
Before we test Combustion, let’s check our Analyzer; Turn “ON” the Analyzer and let it warm up. Hold the probe in the air and read the O2. It should read approximately 21%. If not, the O2 sensor in your analyzer must be calibrated or changed.
1.) Start the boiler and set the boiler into HIGH fire.
2.) Press the round INSTALLER button. Enter the access code “054” press OK. Press the RIGHT button to highlight the Manual Operation icon, press OK. Press the OK button while the FAN icon is highlighted to manually fire the system. Press the RIGHT button and move the slide to 100%.
3.) Remove the cap in the exhaust flue pipe; install the probe of the analyzer into the exhaust flue pipe hole in the flue pipe.
4.) If the O2 reading is above 3.9% turn throttle screw CCW to lower the O2, if the reading is below 3.9% turn the throttle CW to increase the O2. Set the boiler into LOW fire. If you are still in high fire just press the LEFT button and move the slide to 1%.
5.) Check the O2 reading in low fire, it should not differ more then 2/10 of a percent.
If the readings between High and LOW fire differ more then 2/10 %, call Triangle Tube Tech Support.
The Challenger Blower is either not responding to the controller, or the controller is not sending a signal.
The test procedure is as follows; all these tests need to be done with the #1 in the right window. Test the controllers output. There should be 26+ volts DC between the black and white wires. If the 4 wire plug are disconnected, there will not be an output to the 120 volt plug. With the 4 wire plug connected, and the #1 in the right window there should be 120 volts AC to the three wire plug to the blower. If either of these conditions is not present, replace the controller. Short of that, it is the blower that will have to be replaced. Be sure to remove all of the parts from the old blower and install them in the new blower. (IE: Gas pipe, Venture, retaining clip, exhaust gasket, and restrictor ring.
The E-11 lockout is many times caused by the Domestic flow switch sticking. If the flow switch sticks, the block temperature increases to a point that the supply sensor cannot read the temperature and the control board thinks that the supply sensor is shorted. Shut off water to the Domestic inlet side, and drain the water from the Domestic side of the system. Remove the flow switch located on the outlet side of the Domestic water at the bottom of the boiler. Clean the flow switch and inspect the brass tee that holds the flow switch for build up. Install a 60 mesh y-strainer on the inlet side of the Domestic water. (Part # CCSTRA01) This will many times stop the E-11 from occurring.
Check the pressure inside of the boiler, if below 7 PSI increase the boiler pressure above 12 PSI, push the reset and unit should start. If system is above 7 PSI, the LWCO needs to be either cleaned or replaced.
Remove water from boiler. Remove LWCO; on the WET side of the LWCO (the part that is in the water) inside the ¼ inch opening there is a small weep hole. The weep hole is about the size of an 18 gauge wire. Find and clean out the weep hole and re-install the LWCO. Fill the boiler with water and restart the system. If this does not correct, replace the LWCO. Side bar NOTE: the system may need to be cleaned or an inhibitor may be needed to be added. See BOILER COMMISSIONING
This will break down into three categories. 1) Is there fire occurring, but not proving? 2) Is the unit not producing fire at all? 3) Fire is established but after a short time (30 seconds)
1) If we are producing fire but not proving, this is a condition of lacking ground or a defective flame signal. The unit MUST have a dedicated power supply from the incoming distribution electrical panel, with a full sized uninterrupted ground.
Be sure to remove the igniter and clean it. If more than 2 years old it would be prudent to replace it. Also check the condition of the orange ignition wire, make sure it has good connections on both the igniter and the ignition transformer. Insure that the wire is not touching any metal.
The flame signal is determined by the ignition transformer. Since we cannot establish a flame, we cannot read the flame signal; therefore check the ignition transformer once again being sure of the condition of the connector on the wires.
2) If we are not producing any flame, then we are missing one of the three ingreedences needed for fire. Ignition, Fuel, and Oxygen. We will attach our manometer to the inlet port on the gas valve; we should have Approxitmilly 6” of pressure for Nat. gas, Approxitmilly 11” for L.P. We should be able to see the spark generated when the unit goes into ignition through the inspection mirror attached to the left side of the heat exchanger. It is normally very visible.
Removing the exhaust pipe from the condensate pan to increase the airflow from the blower. If we ignite then, we are restricted either in the exhaust pipe, or in the heat exchanger. Examine the exhaust pipe and remove the plate from the aluminum block and examine the flue ways for cleanliness.
During the testing with the exhaust pipe there should be a strong order of gas coming from the outlet, if not, with the unit re-assembled, place your manometer on the outlet port of the gas valve. During pre-purge there should be a ½ inch of negative pressure developed. When the ignition cycle begins, the negative pressure should disappear, if it does not it is a defective gas valve.
3) If the unit lights, proves but when the blower begins to slow, the burner goes out. There we have a combustion issue that will require the use of the combustion analyzer. Make sure that at a forced high fire, we have an O2 level of 4.3% and when forced to low fire does not change more than 0.2%.
To find the serial number on a Prestige PA boiler, please look towards the bottom of the right side panel of the unit. The serial number will be PA or PEA followed by 6 digits (e.g. PA123456, PEA123456).
To find the serial number on a Prestige PT boiler, you must remove the front panel. Once removed, the serial number will be visible. The serial number will be PT followed by 7 digits (e.g.PT1234567).
To find the serial number on a Prestige PS boiler, you must remove the front cover, then open the flap on the front of the unit. Once open, you will find the number on the bottom of the flap tab. The serial number will be PS followed by 4-5 digits (e.g. PS1234, PS12345).
To find the serial number on the Challenger, please look towards the top of the right side panel of the unit. The serial number will be 6 digits a dash then 10 alphanumeric characters (e.g. 012345-1234A56789, 012345-1234567890).
To find the serial number on the Marquis, please look towards the middle of the large sticker on the right side panel of the unit. The serial number starts with TH followed by 7-9 alphanumeric character (e.g. THN1234567, THP1234567B).
To find the serial number on the Keystone, please look towards the large sticker on the right side panel of the unit. The serial number starts with K followed by 8 digits (e.g. K12345678).
Please look on the top of the unit to find the serial number. The serial number starts with 1 or 2 letters followed by 4 or 6 digits or has 5 digits with no letters (e.g. A1234, BB1234, S123456, 12345).
Contractors can register their product through InstallerConnect.com to earn points and redeem rewards for each registration. Homeowners can register under homeowner product registration on our website https://triangletube.com/professional-resources/toolbox/product-registration/
Connect Loyalty Program is a contractor-based loyalty program to register products, earn points, and redeem rewards for each registration. Visit here to learn more InstallerConnect.com.
To be included in our list of contractors on our website, we request that you complete the following steps:
-Install a Triangle Tube boiler.
-Register the installed boiler on our website or on the Connect Loyalty Program
-Ensure and submit optimal combustion results.
To be included in our list of preferred contractors on our website, we request that you complete the following steps for 5 products:
-Install 5 Triangle Tube boilers.
-Register 5 installed boilers on our website or on the Connect Loyalty Program
-Ensure and submit optimal combustion results for all 5 boilers.
Below you will see a copy of the service trend sheet. You are free to download this image and make a copy for your own use.
Consumer Alert – Warranty and Technical Support
Triangle Tube designs and manufactures industry leading hydronic heating solutions, including high efficiency boilers, domestic water heaters, heat exchangers, and controls. These products can provide years of service when properly installed. Our commitment to this performance is demonstrated not only in the attention to detail in our engineering and manufacturing, but also in the hundreds of hours of training that we provide our representatives, wholesalers, and installers every year. In addition, we provide technical support to our authorized installers through our Corporate Engineering team, who average over 20 years of experience in the hydronics industry.
We have developed a team of authorized representatives and wholesalers that will provide installers and consumers with the quality product and service that will ensure maximum performance. Triangle Tube stands behind our products through our warranty policy. However, we cannot provide this warranty protection if our products are not purchased through our authorized representatives and wholesalers. Unauthorized sellers (online or otherwise), may be selling discontinued or refurbished models, and cannot visit your home to ensure properly sized and installed equipment. Most online sellers cannot supply references in your neighborhood, and, since they do not perform the installation, will deny responsibility for any problems.
By selecting an authorized representative, wholesaler, or installer you will receive:
- A responsible, professional installer with years of good experience that you can verify, and who isclose to home.
- A contractor with a solid business who visits your home before they quote a price and who will stand behind the product after they get paid.
- A contractor that has been trained by Triangle Tube on the product so that they will install it according to specifications.
Therefore, it is the policy of Triangle Tube to provide technical support only to licensed heating technicians installing product supplied by authorized dealers. Triangle Tube will NOT provide technical support for product supplied by unauthorized dealers.
It is also the policy of Triangle Tube to provide a warranty only to product sold by an authorized dealer and installed by a licensed heating technician. Triangle Tube will NOT provide a warranty for our product that is purchased online or through other unauthorized channels, and/or installed by someone other than a licensed heating technician.